Free Calculator · No Signup

Arc-Flash Incident Energy Calculator

Incident energy is the thermal energy an arc would deliver to a surface at a working distance, in calories per square centimetre. It determines the PPE category and the arc-flash boundary that must appear on the equipment label. Two inputs dominate it, and only one is obvious: available fault current, and how long the upstream device takes to clear. Halving clearing time roughly halves incident energy, which is why protection settings matter more to arc-flash exposure than almost anything else.

Run the numbers

The working calculator is free and needs no signup.

OPEN THE CALCULATOR →

The formula

The Lee method models an open-air arc. Incident energy rises with available fault current, with the square of arcing time, and falls with the square of working distance.
Bolted fault currentFrom the fault-current calculation at that point
Clearing timeHow long the upstream protective device takes to interrupt, in seconds
Working distanceDistance from the arc to the worker's face and chest, commonly 18 inches for LV gear
System voltageThe Lee method applies above 600 V; below that, IEEE 1584 empirical models apply

Worked example

Doubling the clearing time from 0.1 s to 0.2 s does not double incident energy — it roughly quadruples it, because energy scales with the square of time. A breaker setting change that shaves 100 ms off clearing can move a task from one PPE category to a lower one without touching the hardware.

Which standard governs this

The theoretical Lee equation is documented in IEEE 1584, which is the governing standard for arc-flash calculation. NFPA 70E sets the workplace requirements: risk assessment, approach boundaries, PPE, and equipment labelling.

What this calculation does not account for

Lee is a theoretical open-air model and is conservative below 600 V, where IEEE 1584's empirical equations fit measured data far better. It does not model arc-in-a-box enclosure effects, electrode configuration or arc gap. This is a screening estimate only. Labelling and PPE selection require a full study by a qualified engineer.

This is a screening estimate. It is here to get you to the right order of magnitude and the right conversation — not to replace a stamped calculation by a qualified engineer.

Common mistakes

Treating a screening number as a labelling result. Using a clearing time from the device curve without accounting for the arcing current being lower than bolted fault current, which can put the device on a slower part of its curve. Assuming higher fault current always means higher incident energy — sometimes it clears the device faster and lowers it.

Related