Free Calculator · No Signup

Voltage Drop Calculator

Voltage drop is the loss along a conductor between the source and the load. It is not a code violation in itself — the NEC states its 3% branch-circuit and 5% total figures as recommendations in informational notes, not requirements — but equipment is rated to operate within a voltage band, and a long run that drops too far will leave a motor starting hard, a contactor chattering, or a drive faulting on undervoltage. On a long feeder it is usually voltage drop, not ampacity, that forces the conductor up a size.

Run the numbers

The working calculator is free and needs no signup.

OPEN THE CALCULATOR →

The formula

VD = (2 × K × I × D) / CM [single-phase]
VD = (1.732 × K × I × D) / CM [three-phase]
KResistivity constant: 12.9 for copper, 21.2 for aluminium, in ohm-cmil/ft
ILoad current in amperes
DOne-way circuit length in feet
CMConductor cross-section in circular mils
2 or 1.732Accounts for the return path: two conductors single-phase, the square root of three for three-phase

Worked example

A 100 A three-phase load at 480 V, 150 ft away, on 2 AWG copper (66,360 cmil):

VD = (1.732 × 12.9 × 100 × 150) / 66,360 = 5.05 V

As a percentage: 5.05 / 480 = 1.05%. Comfortably inside 3%.

Move the same load to 400 ft and it becomes 13.5 V, or 2.8% — still inside the limit, but with nothing left for the branch circuit beyond it.

Which standard governs this

The K-factor method is the standard hand calculation. NEC 210.19(A) and 215.2(A) informational notes give the 3% branch and 5% total figures. For exact work, IEEE Std 141 (the Red Book) covers the full method with reactance included.

What this calculation does not account for

This is a resistance-only calculation. It ignores conductor reactance, which matters on larger conductors and longer runs — above roughly 250 ft, or above about 4/0, the reactive component starts to dominate and this method under-reads. It also assumes a 75°C conductor temperature and a balanced load.

This is a screening estimate. It is here to get you to the right order of magnitude and the right conversation — not to replace a stamped calculation by a qualified engineer.

Common mistakes

Using one-way distance where the formula wants it and then doubling it again — the 2 and the 1.732 already account for the return path. Sizing to ampacity first and never checking drop on a long run. Applying the single-phase formula to a three-phase circuit, which over-states drop by about 15%.

Related