Free Calculator · No Signup

Transformer Sizing Calculator

Convert a kW load to the kVA rating you need, round to the nearest standard ANSI/IEEE C57.12.00 nameplate, and get full-load amps.

Transformer Size

Rounds up to the nearest standard kVA nameplate rating. Add your own margin for future load growth — this doesn't assume any.

Transformers are rated in kVA — apparent power — while loads are usually described in kW, real power. The difference is power factor, and ignoring it is how a transformer ends up undersized on day one. Once you have the kVA figure you cannot simply order it: transformers are built to a standard series of nameplate ratings, so the practical answer is always the next size up.

The formula

kVA = kW / PF
FLA = kVA × 1000 / (1.732 × V) [three-phase]
FLA = kVA × 1000 / V [single-phase]
kWReal power drawn by the load
PFPower factor, between 0 and 1
VLine-to-line secondary voltage
FLAFull-load amperes at the nameplate rating

Worked example

A 400 kW load at 0.85 power factor:

kVA = 400 / 0.85 = 470.6 kVA

The standard series runs 300, 500, 750, 1000 — so the unit specified is 500 kVA.

At 480 V three-phase: FLA = 500 × 1000 / (1.732 × 480) = 601 A.

Which standard governs this

Standard nameplate ratings come from ANSI/IEEE C57.12.00. Loading practice beyond nameplate is covered by IEEE C57.91, which governs how far and how long a unit may be run over rating before insulation life is affected.

What this calculation does not account for

This sizes for steady-state load only. It does not account for future growth, harmonic heating, non-linear load, or motor starting, all of which argue for headroom. It also says nothing about impedance, which is the other half of a transformer specification and the one that sets downstream fault current.

This is a screening estimate. It is here to get you to the right order of magnitude and the right conversation — not to replace a stamped calculation by a qualified engineer.

Common mistakes

Sizing on kW and never dividing by power factor, which under-sizes by however far PF sits below unity. Sizing exactly to calculated load with no growth allowance. Choosing on kVA alone and leaving %Z to the supplier, which is how switchgear ends up under-rated for the fault current the transformer can deliver.

Embed this calculator

Writing about this, or teaching it? Paste the snippet below into any web page to add a working copy of the calculator above. It is free, runs entirely in the reader’s browser, sends nothing anywhere, and links back to this page for the method.

<div class="vf-calc-widget" data-calc="transformer-sizing"></div>
<script src="https://voltfield.org/embed/calculator-widget.js" async></script>

Also available: voltage-drop, transformer-sizing and power-factor. Change data-calc to switch.

Related

Get new calculators and guides by email

One short email when a new guide or calculator is published, at most once a month. Your address is used for nothing else.