Power Fundamentals

kW vs. kVA Explained

Loads are described in kW. Transformers, generators and UPS systems are rated in kVA. Mixing the two up is the most common way a piece of power equipment ends up undersized on day one.

By Voltfield Editorial Team·Published September 29, 2026·How we source & verify this
A panel-mounted digital power meter
Panel power meter (illustration)

Key takeaways

  • kW is real power; kVA is apparent power. kVA = kW ÷ power factor, and kVA is never smaller than kW.
  • Size transformers on kVA: a 400 kW load at 0.85 power factor needs about 471 kVA, not 400.
  • A genset's kW rating already assumes 0.8 power factor, so don't apply it twice; check both the kW and kVA ratings of a UPS.
On this page · 7 sections
  1. The power triangle
  2. How much kVA per 100 kW
  3. Converting kW to kVA and amps: a worked example
  4. Why equipment is rated in kVA
  5. Where power factor costs money
  6. Common mistakes
  7. Frequently asked questions

kW (kilowatts) is real power: the part of the electrical supply that does work, turning a motor shaft, heating a resistor or running a server. kVA (kilovolt-amperes) is apparent power: the voltage multiplied by the current actually flowing, whether or not all of that current is doing work. The ratio between them is the power factor.

kVA = kW ÷ PF   ·   kW = kVA × PF

At a power factor of 1.0 the two are the same number. Below 1.0, kVA is always the larger one, because some of the current is flowing back and forth to set up magnetic and electric fields (reactive power, measured in kVAR) rather than delivering energy to the load. That current still has to be carried by every cable, breaker and transformer winding in the path.

The power triangle

Real power (kW) and reactive power (kVAR) are at right angles to each other, and apparent power (kVA) is the hypotenuse:

kVA² = kW² + kVAR²   ·   PF = kW ÷ kVA = cos φ

The angle φ is the phase shift between voltage and current. Inductive loads such as motors and transformers draw current that lags the voltage. Capacitive loads draw current that leads it. Either way, the further φ is from zero, the more kVA it takes to deliver the same kW.

How much kVA per 100 kW

PFkVA / 100 kWkVAR / 100 kW
1.00100.00.0
0.95105.332.9
0.90111.148.4
0.85117.662.0
0.80125.075.0
0.70142.9102.0

Every figure in the table is arithmetic from the two formulas above: kVA = 100 ÷ PF, and kVAR = √(kVA² − 100²). Going from 0.95 to 0.80 raises the apparent power by about 19% for exactly the same useful work.

Converting kW to kVA and amps: a worked example

A 400 kW load at 0.90 power factor, fed at 480 V three-phase:

Drop the power factor to 0.80 and the same 400 kW becomes 500 kVA and 601 A: 66 more amps through every conductor, for no extra work done. For single-phase circuits, leave out the 1.732: I = kVA × 1000 ÷ V.

Three-phase: I = kVA × 1000 ÷ (√3 × VLL)   ·   Single-phase: I = kVA × 1000 ÷ V

Why equipment is rated in kVA

A transformer or alternator does not know what the load is doing with the current. Its winding losses, and therefore its heating, scale with the current squared (I²R), and its core losses scale with voltage. Both depend on volts and amps, not on the phase angle between them. So the limit is stated in volt-amperes, and the equipment can deliver its full rating in kW only when the load's power factor is 1.0.

Loads, on the other hand, are described by the work they do, and energy is billed in kWh. That is why the conversion has to happen at the point where a load list meets an equipment rating.

Transformers

Size on kVA: divide the load in kW by the expected power factor, then go up to the next standard nameplate from ANSI/IEEE C57.12.00. The 444 kVA example above lands on a 500 kVA unit. The Transformer Sizing Calculator does this step and returns full-load amps. Reading the result back off a real unit is covered in How to Read a Transformer Nameplate.

Generators

Generator sets carry both numbers because they have two limits. The engine limits kW, since real power is what burns fuel. The alternator limits kVA, since that sets winding current. By industry convention, three-phase gensets are rated in kW at 0.8 power factor, so a 2,000 kW set is a 2,500 kVA set. A load at 0.9 power factor can use the full kW rating. A load at 0.7 hits the alternator's kVA limit before the engine's kW limit. Generators also tolerate leading (capacitive) power factor poorly, so a lightly loaded site with large filter capacitors can have voltage-regulation problems even though it is well inside the kW rating. Fuel burn tracks kW, which is what the Generator Runtime Calculator works from. The full sizing method is in How to Size a Standby Generator.

UPS systems

A UPS has a kVA rating and a kW rating, and either one can be the binding limit. Older three-phase designs were commonly rated at 0.8 output power factor, so a 500 kVA unit could only deliver 400 kW. Many current designs are rated at 0.9 or 1.0. Modern server power supplies with active power-factor correction typically run close to unity, so for IT load the kW rating is usually the one that runs out first. Always check the kW figure, not just the kVA on the front of the datasheet. The full method, including redundancy and battery runtime, is in How to Size a UPS.

The shortcut that goes wrong: treating kW and kVA as interchangeable works only near unity power factor. It is close enough for a rack of modern servers and badly wrong for a motor-heavy mechanical plant, where power factor at part load can sit well below 0.8.

Where power factor costs money

Beyond equipment sizing, low power factor shows up on the utility bill. Some tariffs bill demand in kVA rather than kW, and others add a charge when power factor falls below a threshold set in the tariff. The fix is usually local correction: capacitor banks, or active filters where harmonics are present, that supply the reactive power on site so it is no longer drawn through the utility service. The Power Factor Correction Calculator sizes the kVAR needed to reach a target power factor and shows how much apparent power is released.

Common mistakes

Frequently asked questions

How do I convert kW to kVA?

Divide kW by the power factor: kVA = kW ÷ PF. For example, 400 kW at 0.9 power factor is 444.4 kVA. If the power factor isn't known, 0.8 is the conservative assumption most generator and older UPS ratings use.

Is kVA always bigger than kW?

kVA is never smaller than kW. The two are equal at a power factor of 1.0, and kVA grows larger as power factor drops, because more current is needed to deliver the same real power.

Why are generators rated at 0.8 power factor?

It is the industry convention for three-phase generator sets. The engine limits real power (kW) and the alternator limits apparent power (kVA), and stating the kW rating at 0.8 power factor fixes the relationship between the two: kVA = kW ÷ 0.8.

Why are transformers rated in kVA instead of kW?

A transformer's heating depends on the current in its windings and the voltage across its core, not on the power factor of the load. The same current heats the windings equally whether it is doing useful work or not, so the rating is stated in volt-amperes.

Next steps

kW-to-kVA conversion is the first step in almost every sizing exercise on this site. The POD & Skid Designer applies it when checking a power block against its target load, and the Data Center Power Equipment pillar page covers the transformers, switchgear, UPS and generators whose ratings it feeds into.

Equipment

Share this guide:
Cite or link to this guide

Free to quote with attribution. Suggested citation: Voltfield Editorial Team, “kW vs. kVA Explained,” Voltfield, updated September 29, 2026. https://voltfield.org/guide-kw-vs-kva.html

Get new guides by email

One short email when a new guide or calculator is published, at most once a month. Your address is used for nothing else.