Switchgear & Protection

Ground-Fault Protection Explained

On a 480Y/277 V service, an arcing ground fault can burn for minutes while drawing less current than the main breaker's rating. Equipment ground-fault protection exists to catch it. Here's what NEC 230.95 requires, how GFP senses a fault, and why it's easy to get wrong.

By Voltfield Editorial Team·Published September 29, 2026·How we source & verify this
A draw-out air circuit breaker
Air circuit breaker (illustration)

Key takeaways

  • On a 480Y/277 V service, an arcing ground fault can burn while drawing less current than the main breaker's rating.
  • Equipment ground-fault protection (GFP) is set in hundreds of amps to protect equipment; it is not a GFCI for people.
  • GFP on the main alone means any downstream ground fault trips the whole service, and the on-site performance test is required.
On this page · 8 sections
  1. Why overcurrent protection isn't enough
  2. What NEC 230.95 requires
  3. How GFP senses a ground fault
  4. Coordination: why GFP on the main alone is a problem
  5. GFP is not GFCI
  6. Data center considerations
  7. Common mistakes
  8. Frequently asked questions

Ground-fault protection of equipment (GFP or GFPE) detects current flowing to ground and opens the circuit before an arcing fault can destroy the equipment. It isn't a people-protection device. It's set in hundreds of amps, not milliamps, and its job is to stop a low-level arcing fault that ordinary overcurrent protection can't see.

Why overcurrent protection isn't enough

A bolted fault draws enormous current and trips a breaker almost instantly. An arcing ground fault is different: the arc itself has voltage across it, and the fault path has impedance, so the current can be a small fraction of the bolted value. On a 480Y/277 V system there's enough voltage to sustain that arc.

Take a 3,000 A service main and an arcing ground fault drawing 2,000 A. That's below the breaker's rating, so its phase overcurrent protection will never trip. The arc keeps burning, destroying the switchgear, until something else gives out. A GFP relay set at 1,200 A sees the 2,000 A going to ground and opens the breaker within its time delay.

Lower-voltage systems such as 208Y/120 V are less prone to sustained arcing faults, which is why the NEC requirement applies above 150 V to ground.

What NEC 230.95 requires

Similar requirements apply to large feeder disconnects (NEC 215.10) and building disconnects (240.13) where there's no GFP upstream. Health care facilities need an additional level of ground-fault protection on feeders, so that a downstream fault doesn't take out the whole service.

Emergency systems work differently. The NEC doesn't require equipment GFP on an emergency system's alternate source, because tripping the generator on a ground fault defeats the point of having it. Instead, it requires ground-fault indication, so the fault is alarmed and can be found.

How GFP senses a ground fault

MethodHow it works
ResidualCTs on each phase and on the neutral. Their sum is zero unless current is leaving through ground. Common in breaker trip units.
Zero-sequenceOne core-balance CT around all the phase and neutral conductors. Sensitive, but limited by the window size.
Ground returnA CT on the main bonding jumper measures the current returning through it. Simple, but it only works on a single-source service.

The neutral CT is the part most often wired wrong. If it's missing, reversed or on the wrong side of the neutral-to-ground bond, normal unbalanced neutral current looks like a ground fault and the system trips on load. Or, just as bad, a real fault is missed.

Coordination: why GFP on the main alone is a problem

GFP is required at the service. If that's the only level of ground-fault protection, the main is the only device that can clear a low-level ground fault anywhere downstream. A fault on one branch circuit takes down the entire service. Selectivity needs GFP on the feeders as well, with settings and time delays graded so the device nearest the fault trips first. The coordination study should include the ground-fault curves, not just the phase curves.

Multiple sources make it harder. In a main-tie-main lineup, or with a generator bonded at the switchgear, neutral current can return by more than one path. A simple residual scheme then sees current that isn't a fault and trips, or misses current that is. These systems need a modified differential ground-fault scheme, designed around the actual neutral and bonding arrangement.

GFP is not GFCI

A ground-fault circuit interrupter (GFCI) protects people. It trips at around 5 mA, and UL 943 requires Class A devices to trip at 6 mA or less, far below the level that could stop a heart. Equipment GFP protects equipment, with pickups in the hundreds of amps. One can't substitute for the other.

Data center considerations

Common mistakes

Frequently asked questions

When is ground-fault protection required by the NEC?

NEC 230.95 requires equipment ground-fault protection on solidly grounded wye services with more than 150 V to ground, for each service disconnect rated 1,000 A or more. In practice, that means large 480Y/277 V services. Similar rules apply to large feeder and building disconnects.

What are the NEC 230.95 GFP settings?

A maximum pickup of 1,200 A, and a maximum time delay of one second for ground-fault currents of 3,000 A or more. Lower settings are allowed, and are often needed for coordination with downstream devices.

What is the difference between GFP and GFCI?

A GFCI protects people and trips at a few milliamps. Class A devices trip at 6 mA or less under UL 943. Equipment GFP protects equipment from arcing ground faults, with pickups in the hundreds of amps. They aren't interchangeable.

Why does GFP trip when there is no ground fault?

Usually because of the neutral: a missing or reversed neutral CT, a CT on the wrong side of the neutral-to-ground bond, or a multi-source system where neutral current returns by more than one path. The required on-site performance test is where these errors are normally found.

Next steps

The switchgear reference covers the service and distribution equipment where GFP is installed, and Switchgear Components covers the trip units and current transformers it's built from.