Cables & Conductors

Cable Ampacity Derating Explained

The ampacity table assumes three conductors in a raceway at 30°C. Real installations rarely match either assumption, and the terminations may cap the answer anyway. Here is how to get from the table value to the number you can actually use.

By Voltfield Editorial Team·Published September 29, 2026·How we source & verify this
Coils of insulated low-voltage power cable
Low-voltage power cable (illustration)

Key takeaways

  • NEC Table 310.16 assumes no more than three current-carrying conductors at 30°C ambient; where either fails, the value must be reduced.
  • Correct for ambient temperature and adjust for conductor count, then cap the result at the terminal temperature rating.
  • 90°C insulation helps by absorbing derating, but 75°C terminations can still limit the final ampacity.
On this page · 7 sections
  1. Step 1: Start from the right column
  2. Step 2: Correct for ambient temperature
  3. Step 3: Adjust for more than three current-carrying conductors
  4. Step 4: Cap at the terminal rating
  5. Worked examples
  6. Common mistakes
  7. Frequently asked questions

Ampacity is the current a conductor can carry continuously without exceeding its insulation temperature rating. The NEC's ampacity tables, most often Table 310.16, give a starting value that assumes no more than three current-carrying conductors in a raceway or cable, at an ambient temperature of 30°C. Where either assumption fails, the table value has to be reduced.

Usable ampacity = table ampacity × ambient correction × conductor-count adjustment, capped by the terminal rating

Step 1: Start from the right column

Table 310.16 has columns for 60°C, 75°C and 90°C insulation. A copper 4/0 conductor, for example, is listed at 195 A, 230 A and 260 A respectively. For a 90°C-rated conductor such as THHN or XHHW-2, derating can start from the 90°C column. That's the practical value of 90°C insulation: it absorbs derating that would otherwise force a bigger conductor.

Step 2: Correct for ambient temperature

Above 30°C, the conductor has less headroom before it reaches its insulation limit. NEC 310.15(B) gives the correction factors:

Ambient75°C column90°C column
26–30°C1.001.00
31–35°C0.940.96
36–40°C0.880.91
41–45°C0.820.87
46–50°C0.750.82

Raceways and cables exposed to sunlight on or just above a rooftop run much hotter than the surrounding air, and the NEC adds a temperature adder for the case where they sit very close to the roof surface. Hot aisles, plenums and equipment yards deserve the same scrutiny.

Step 3: Adjust for more than three current-carrying conductors

Conductors bundled together can't shed heat as well. NEC 310.15(C)(1) reduces ampacity when a raceway or cable holds more than three current-carrying conductors:

Current-carrying conductorsAdjustment
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Equipment grounding conductors don't count. The neutral of a balanced three-phase circuit usually doesn't either, but it does count when most of the load is non-linear, such as server power supplies or drives, because it carries triplen harmonic current. The harmonics guide explains why. Short raceway nipples of 24 inches or less are exempt from adjustment.

Step 4: Cap at the terminal rating

A conductor is only as good as what it's connected to. Under NEC 110.14(C), the final ampacity can't exceed the value in the column matching the lowest-rated termination, which is usually 75°C for equipment rated over 100 A, and often 60°C for smaller equipment unless it's marked otherwise. Derating is done from the 90°C column, but the result is then compared against the 75°C (or 60°C) value, and the lower number wins.

Worked examples

Nine 10 AWG copper THHN conductors in one conduit, 40°C ambient, 75°C terminals.

A 4/0 copper feeder, four current-carrying conductors (the neutral counts, for non-linear load), 40°C ambient.

Without the correction and adjustment, the same 4/0 feeder would be sized as a 230 A conductor, 41 A more than it can actually carry. The same derating also interacts with the continuous-load rules, which size conductors at 125% of continuous load before derating is compared.

Check the edition. Table values and section numbers are quoted from recent NEC editions. Section numbering in 310.15 was reorganized in 2020, so older references (310.15(B)(2)(a), 310.15(B)(3)(a)) point to the same factors under different numbers.

Common mistakes

Frequently asked questions

What is ampacity derating?

Ampacity derating reduces a conductor’s table ampacity to account for conditions hotter than the table assumes: an ambient temperature above 30°C, and more than three current-carrying conductors in a raceway or cable. Both factors are multiplied against the table value.

Can I use the 90°C ampacity column?

For derating, yes, if the conductor is rated 90°C. The derated result must then be compared with the ampacity in the column matching the lowest-rated termination, usually 75°C, and the lower value used (NEC 110.14(C)).

Does the neutral count as a current-carrying conductor?

Not usually on a balanced three-phase circuit, but it does when most of the load is non-linear, such as server power supplies, LED drivers or drives, because triplen harmonic currents add in the neutral. Equipment grounding conductors never count.

What is the adjustment factor for 4 to 6 conductors?

80% of the table ampacity, under NEC 310.15(C)(1). It falls to 70% for 7 to 9 conductors and 50% for 10 to 20.

Next steps

The Data Center Cable & Busbar reference covers the conductors and busway involved, and the Cable Ampacity Calculator looks up table values and checks conduit fill.

Equipment

Share this guide:
Cite or link to this guide

Free to quote with attribution. Suggested citation: Voltfield Editorial Team, “Cable Ampacity Derating Explained,” Voltfield, updated September 29, 2026. https://voltfield.org/guide-cable-ampacity-derating.html

Get new guides by email

One short email when a new guide or calculator is published, at most once a month. Your address is used for nothing else.